Require Engineered Support

CAUTION!! ⚠️

This is a Public Service Announcement


Have you been provided a document claiming that rooftop duct supports are “pre-engineered to comply with wind loading”? If so, DO NOT BE FOOLED!!!

Other manufacturers make false claims about the wind rating of their systems. Some even provide a blanket statement to their products…THIS IS FALSE!!!

Do not accept a marketing flyer as an engineering document

It is impossible to provide a blanket wind rating to roof supports. There are just too many variables:
  • Risk factor
  • Building category
  • Building height
  • Size of items being supported
  • Mount height off the roof
  • Weight
  • Length of run
  • Etc. 

ENGINEERING REPORT

We had our engineer run calculations to test the claims of a concrete duct support manufacturer, and this is what we found:

For a 36” x 36” duct to resist the overturning moment due to lateral forces caused by wind on a 40’ tall building (Risk Category 2), with 48” support spacing mounted 24” above the roof surface.

EACH BASE WOULD HAVE TO WEIGH 380lbs!

Conclusion: Non-penetrating or Free-Standing supports WILL NOT WORK in most situations. 

SOLUTION: Require an Engineered System for all roof mounted items. 

An engineered system by Rooftop Support Systems, a Division of Eberl Iron Works. 

Strategically located anchor points allow for roof penetrations to be minimized while still meeting the project requirements.  